Abstract

To address the serious harmonic problem of grid connected current in photovoltaic grid-connected inverter, a harmonic suppression strategy based on Repetitive and PI control is proposed in this thesis. According to this strategy, the mathematical model of LCL photovoltaic grid-connected inverter is established with the harmonic mechanism analyzed, the repetitive and PI control is added into the current controller, and the capacitive-current feedback is added to enhance the system damping. Furthermore, it puts PI control on the inner loop and the repetitive control on the outer loop to improve the dynamic performance and achieve the harmonic suppression of the system. Moreover, the simulation results show that this method improves the dynamic response ability of the system, and effectively suppress the grid-connected current harmonics as THD of grid-connected current is 19.65% lower than that of PI controller.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.