Abstract

The harmonic current of the Le Blanc transformer of the Taiwan railway system is measured to determine how it reduces the power supply capacity to the trolley (nonlinear load). Improvements to the harmonic current in point-of-common-coupling (PCC) after adding the double-tuned filter to the load side, are also described.