Abstract

This paper presents a novel approach for harmonic state estimation for unbalanced three-phase distribution systems using Phasor Measurement Units (PMUs), considering the presence of harmonic sources connected to the system. Harmonic branch currents in rectangular coordinates are the state variables to be estimated by the proposed methodology. Harmonic voltages and branch currents phasors are measured at monitored buses by PMUs. For the non-monitored buses, load pseudomeasurements are considered as inequality constraints in a proposed optimization problem solved via Safety Barrier Interior Point Method. The main contribution of the method is providing satisfactory estimation results considering non-fully observable power distribution networks with long feeders, requiring a small number of field measurements. Tests on the modified Baran and Wu's 33-bus test system are used to validate the methodology and demonstrate its effectiveness on evaluating power quality indexes, identifying harmonic sources and monitoring harmonic components and their propagation through the network.

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.