Abstract

In this paper, a novel autotransformer with a reduced kilovolt-ampere rating is presented for harmonic current reduction in twelve-pulse ac-dc converter-fed vector-controlled induction motor drives (VCIMDs). Different transformer arrangements for 12-pulse-based rectification are also studied and a novel harmonic mitigator capable of suppressing fifth, seventh, and 11th (most dominant harmonics) in the supply current is presented. The design procedure for the proposed autotransformer is presented to show the flexibility in the design for making it a cost-effective replacement suitable for retrofit applications, where presently a six-pulse diode bridge rectifier is being used. The effect of load variation on VCIMD is also studied to demonstrate the effectiveness of the proposed harmonic mitigator. A set of power-quality indices on input ac mains and on a dc bus for a VCIMD fed from different 12-pulse ac-dc converters is given to compare their performance.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.