Harmonic is an important factor affecting the quality of the power transmission system. caused by non-linear loads and power conversion devices. In this research, several train simulation samples of the city line Airport Rail Link (ARL) electric train were used to simulate the effects of harmonics on the power electric substation (ESS) by calculating the Total Harmonic Distortion of voltage (THDv) and current (THDi). Then compared with IEEE519-2014 standards to indicate the quality of power found that THDi 35th–50th exceeds the standard. In addition, the comparison of the harmonic reduction effect of the sample train from the single tuned passive filter designs of 3rd, 5th, 7th, and 11th showed that the 11th filter was able to keep the THD within the standard.

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.