Abstract
An in-depth study of the harmonic orders inherent in a power system network is required before mitigation techniques are adopted. This paper studied the harmonic orders of the 33 kV Abuja Steel Feeder modeled as a harmonic source using measured data. Readings of kW, kVar, kV and Hz were obtained using power quality analyzer (PQube) to identify the trend and the harmonic unbalance on the feeder. Electrical Transient Analyzer Program (ETAP) software package was deployed to perform Discrete Fast Transform (DFT) while the input parameters were the resultant relative amplitudes and phase angles for both the current and voltage source models. The current source model spectrum of the feeder under study revealed that the 11 th and 13 th harmonic orders have the highest percentage of amplitude relative to the fundamental compared to the other harmonics. On the other hand, the voltage source model spectrum showed that the 14 th , 15 th , 16 th , 17 th , 32 nd , 33 rd and 34 th harmonic orders have higher percentage of relative amplitude. However, only the 3 rd and 5 th harmonic orders were found to cause severe harmonic distortion of voltage and current after harmonic analysis and frequency scan were performed on the ETAP platform. Keywords: Harmonic order; Power quality; Transmission grid; ETAP; Tuned filters
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.