Abstract
This work presents an alternative method of measuring the equivalent impedance of an electric power network by injecting a short time current waveform based on Modulated Gaussian Signal. The frequency domain measurement of the equivalent impedance of an electric network is an important issue to correctly design harmonic filters and capacitor banks, detect resonance and antiresonance frequencies and evaluate the harmonic penetration and emission limits. The method proposed in this paper uses the Sliding Window Recursive Discrete Fourier Transform (SWRDFT) to extract the harmonic components of the measured voltage due to the injection of the short time current into the network. The proposed method was tested with different electric system topologies and the estimated impedance was compared with the impedance estimated by other methods found in the literature. Real time simulation using Hardware-in-the-Loop (HIL) methodology, as well as experimental results are presented in this paper.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.