Abstract
Results of using SPICE simulation software to study the harmonic impact of variable speed air conditioners (VSAC) on a typical residential power system are presented. Results show that IEEE 519-1990 limit of 5% voltage total harmonic distortion is exceeded either at service entrances to residential homes on a single-phase lateral when 33% of the homes on that lateral contain VSACs, or on the 12.47 kV distribution feeders when 9% of the homes throughout the entire system contain VSACs. >
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.