Abstract

Based on the inherent characteristic of the carrier-based pulse-width modulation converters, the response of the first carrier frequency harmonic (FCFH) current in the voltage source converter (VSC)-based high-voltage direct current (HVDC) transmission system is analysed under different fault conditions in this paper. A new protection scheme for the VSC-based HVDC transmission systems is proposed based on the FCFH currents. By extracting the harmonic currents at both the endings of the DC transmission cable, the fault type can be identified. The VSC-based HVDC test system is modelled in the PSCAD/EMTDC and the proposed protection scheme is evaluated with a variety of values of the fault resistance and the fault locations. Comprehensive test studies show that the performance of the proposed protection scheme is inspiring. It can recognise the internal and the external faults correctly.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.