Abstract

In recent years, sinusoidal waveform of the current and voltage disturbs in the electrical distribution system because of the due to the increasing number of non-linear loads. Many standards of IEC and IEEE standards have been published in order to limit the voltage and current waveform distortion. The operators of the electricity distribution network widely use the power quality monitoring systems at the point of common connection (PCC). It has been identified that there are substantial number of harmonic currents excess of the standards transferred to the grid according to the data obtained from power quality monitoring systems. In case of exceeding the limits specified in the standards, there is a need to determine the network and customer responsibilities for the implementation of required sanctions. In this study, using recorded data at the PCC of a medium voltage electrical distribution system, voltage and current harmonic distortion responsibilities of the network and customer are determined by the improved harmonic current vector method. Up-to-date load model based on field measurement which provides more accurate results has been used instead of the constant load impedance in the proposed method.

Highlights

  • In addition to the known harmonics sources, the wide spread use of power electronic devices cause to injection of more harmonic currents in the electrical distribution network

  • To avoid an increase in waveform distortion of the electricity distribution network, some harmonic currents restrictions have been imposed on the production stage of the electrical devices according to standards

  • This study proposes a new method, which is based on measurement of current and voltage at the point of common connection (PCC), in order to determine the responsibilities of the network and costumer

Read more

Summary

Introduction

In addition to the known harmonics sources, the wide spread use of power electronic devices cause to injection of more harmonic currents in the electrical distribution network. Gündoğdu the network causes the network’s voltage to become harmonic as a result of the harmonic voltage drop at the network impedance In this case, even if the linear load is connected to the network, harmonic currents will continue to flow reference measurement point [1]. Harmonic Current Method, which is modeled by Norton equivalent circuit of the customer and the network for a specific harmonic degree, is considered theoretically correct, it shows some practical shortcomings [12]. Instead of the reference impedance method, use of harmonic current method with the approach to updating the load impedances online by using the field measurements will provide more accurate results. This study proposes a new method, which is based on measurement of current and voltage at the PCC, in order to determine the responsibilities of the network and costumer. After the processing of the data collected from the PCC for a long-time period, the responsibility of the customer and the network at the PCC and current and voltage THD values have been obtained

Harmonic Vector Method with Reference Impedance
Harmonic Voltage Contributions
Harmonic Current Contributions
Load Model Using Field Measurements
Proposed Harmonic Contribution Method
Results of the Proposed Method with Field Measurements
Conclusions

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.