The phenomenon of sympathetic interaction between transformers, which is very likely to occur when a transformer is energised onto a system to which there are other transformers already connected, changes significantly the duration and the magnitude of the transient magnetising currents in the transformers involved. This phenomenon is discussed in the paper, with the harmonic content of the transient currents and its associated overvoltages being analysed. It is shown that the importance of taking into consideration the saturation characteristics of the transformers already in operation when studying transformer transient inrush.

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.