Abstract

Abstract The paper presents a new formulation of harmonic current injection of the 6‐pulse uncontrolled bridge rectifier with commutation impedance. In cooperation with a train simulator developed earlier, the proposed harmonic source model is applied in a harmonic analysis program to comprehensively simulate the harmonic penetration in the Blue Line of Taipei Rapid Transit Systems (TRTS). Both frequency scans and harmonic distortion calculations were performed for various system component models. Simulation results indicated that both the voltage and current harmonic distortions in the Blue Line of TRTS were improved by use of 24‐pulse rectifiers. The application of further harmonic suppression schemes in traction networks to alleviate the harmonic distortions can be achieved using the simulated results.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.