Based on the synchronous machine in AC-DC-AC Frequency speed drag System, a new power supply method of phase shifting combination is proposed by a detailed study of the impact in the power grid harmonics. With regard to the main Motor drive system of hot-rolling finishing mills, a large number of varying parameters quantitative analysis is made respectively for power load, LC filter, pulse-width modulation circuit and transformer, in which the grid side harmonic rate and waveform distortion rate is focused on. The simulation results show that the power supply method with reasonable parameters design of the drag system can be drastically reduce the grid side harmonic interference that the total harmonic distortion is suppressed within 4.0%. Results of this study provides an effective method for the design of the factory drag system, reactive power compensation system as well as fault diagnosis of electric drag system.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.