Abstract

In order to ensure the safe and stable operation of the large power grid with high proportion of renewable energy access, the automatic voltage control (AVC) system of the new energy power station is very important. The control strategy of the AVC and the response characteristics of the voltage and reactive power regulating equipment will affect the AVC regulation effect directly. However, the pure digital simulation software cannot simulate its actual response characteristic. This paper established a hardware in loop (HIL) testing platform based on RT-LAB real-time simulation system. The real AVC controller and the real static var generator (SVG) controller hardware are connected to RT-LAB testing platform via I/O physical interface and MODBUS communication, and the HIL coordinated simulation testing scheme is studied based on FPGA of RT-LAB. With established testing platform, the voltage regulating characteristic and reactive power replacement capacity of AVC control strategy is verified.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.