Abstract

Without zero-crossings, dc series arc faults result in much more serious safety threats. As the dc voltage level rises and the system capacity increases, series arc faults appear in dc systems more frequently. To eliminate their damages, specific arc fault circuit interrupters (AFCI) should be developed. In this paper, two kinds of dc systems are considered in the designed experimental setup. Firstly, a dc simulated source with the ac-dc-dc structure is connected to a resistor. This source could act as a constant voltage or photovoltaic (PV) source by operating in different U-I output modes. Then a real PV array outputting the nonlinear U-I output curve is also conducted as a comparison. Next, a simple detection algorithm is proposed based on the established time-domain detection variable. Finally, this series arc fault detection algorithm is implemented using a digital signal processing (DSP) chip. The performance of this hardware behaves satisfying under various system transitions and multiple arc fault conditions with diverse operation points and current levels.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.