Abstract

In this paper, the Linear Time Invariant (LTI) and Linear Time Periodic (LTP) models of two different implementations of the DDSRF-PLL in the presence of voltage imbalance are derived analytically. The accuracy of the models is investigated with time domain simulations, frequency scans, and stability analysis. On top of this, a guideline for properly choosing between LTI and LTP models for stability assessment of the DDSRF-PLL according to the degree of grid voltage imbalance is proposed. Furthermore, it is revealed that, depending on the DDSRF-PLL implementation, the positive-sequence voltage might also cause LTP dynamics, rendering the LTI model inaccurate even when the imbalance is low.

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.