Abstract

For the neutral point not grounded characteristics of underground power supply system in coal mine, this paper studied common mode equivalent circuit of underground PWM inverter, and extracted parasitic parameters of interference propagation path. The author established a common mode and differential mode model of underground inverter. Taking into account the rise time of PWM, the simulation results of conducted interference by Matlab software is compared with measurement spectrum on the AC side and motor side of converter, the difference is consistent showing that the proposed method has some validity. After Comparison of calculation results by Matlab simulation ,it can be concluded that ungrounded neutral of transformer could redue common mode current in PWM system, but not very effective, the most efficient way is to increase grounding impedance of inverter and motor. DOI: http://dx.doi.org/10.11591/telkomnika.v11i9.3267

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.