Abstract

This paper examines the performance of the grounding system of a gas meter station, which is solidly connected to a nearby power plant via metallic pipelines located in a common corridor with overhead transmission lines exiting the power plant. This problem is unique because the metallic pipe connecting the meter station to the power plant is subjected to induction from the overhead transmission lines and, at the same time, the meter station is also near the power plant. To evaluate accurately the performance of the meter station grounding system, the induced effects on the pipeline due to the presence of the overhead transmission lines and the influence of the nearby power plant grounding system must be considered. This paper presents a detailed study of this problem. The grounding systems of the meter station and the power plant are modeled as well as the pipeline/transmission line corridor. The performance of the meter station grounding system is evaluated, accounting for the magnetic field induction from transmission lines associated with the power plant.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.