Abstract

Actual ground fault tests were conducted to determine the behavior of low-magnitude arcing ground faults in a closed air-filled 13.8-kV terminal chamber. Ground current magnitudes between 10 and 50 A were allowed to flow under various ground fault conditions. The tests that were performed support the value of high-resistance grounding to promote safety and reduce damage to equipment. At higher ground fault current levels the ionization of the air-filled chamber progresses at a rapid rate, and the arc is sustained or phase-to-phase faulting quickly occurs. The lower the ground fault current can be limited the less damage that occurs and the less possibility there is of creating a phase-to-phase fault. The practical consideration appears to be that if ground fault current can be limited to 10 A or less then initial ground faults will either clear themselves or create solid ground paths. This can allow the system to operate until an orderly shutdown procedure can be initiated.

Full Text
Published version (Free)

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call