Abstract
According to the shortcoming of single-phase ground fault line selection method in the resonant grounded system such as the uncertainty of its device by fast compensation with the automatic compensation equipment, an arc suppression and residual flow incremental method is proposed to effectively choose the earth fault line. Firstly, when the single-phase ground fault occurs, the arc suppression coil parameters are adjusted to realize compensation and arc suppression. Then the arc suppression coil inductance values are modulated to make the zero-sequence current of fault line changed, at the same time, the zero-sequence current value is detected and its change will be captured to select the fault line. The simulation experiments prove that the arc grounding over voltage damage can be effectively reduced by arc suppression coil full compensation and fault line can be effectively selected by arc suppression and residual flow increment method. DOI: http://dx.doi.org/10.11591/telkomnika.v11i8.3106
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
More From: TELKOMNIKA Indonesian Journal of Electrical Engineering
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.