Abstract

Many mine power systems operate with a floating neutral or are high-resistance grounded, and earth fault current is no more than a few tens of amperes. Traditional earth-fault-detection methods based on zero-sequence current have poor sensitivity in this case. For improvement, a fault-detection scheme with fault-current and fault-resistance measurement is presented in this paper, which is capable of detecting high-impedance ground faults. The scheme has been verified by electromagnetic-transient-program simulation, and a fault-detection prototype has been developed and tested in the laboratory. Results show that the scheme has high sensitivity and robustness.

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.