Abstract

Coordination of directional relays in large-scale power systems that are multi-loop structured is a complicated and time consuming problem. Therefore, determination of the directional loops and the minimum break point set (MBPS) or a set close to it, which is essential to start relay coordination, is challenging. So far, several heuristics and exact methods have been proposed for the determination of the MBPS. In this paper, a new heuristic method based on a new implementation of depth-first search algorithm is proposed, which considerably facilitates the detection of directional loops (if any) in the network. The proposed method is tested on a 5-bus, four IEEE and four Polish test systems. The results show the efficiency of the proposed method in finding optimal or near-optimal solutions in a rational amount of time.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.