Abstract

A new fault location system based on the travelling wave principle and capable of locating faults on power lines to within /spl plusmn/one tower span (300 m) has been successfully developed and applied to BC Hydro's extensive 500 kV network. Unlike earlier schemes which are based on impedance measurements, its accuracy is not affected by load conditions, high grounding resistance and most notably series capacitor banks. This system measures the time of arrival of a fault-generated travelling wave at the line terminals using the precise timing signals from the Global Positioning System (GPS). Operating experience with the fault locator on lightning related faults indicated highly accurate results were obtained for the majority of the cases. In a few of the lightning-caused disturbances, the system gave anomalous measurements. This paper describes the operation of the system, summarizes the operating experience and explains the observed anomalous measurements.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.