Abstract

The addition of static capacitors for power factor correction on the 4-kv distribution circuits of the Chicago, Ill., system has resulted in the operation of generators at power factors close to unity during light load periods. This introduces a problem of generator stability at low levels of excitation. It is the purpose of this paper to present the results of a study on the behavior of the generators on the Chicago system during these light load periods, and to show to what extent capacitors may be added to the system without resorting to capacitor switching. The paper shows that loss of generator field presents the most serious problem in the operation of generators during such light load periods. The results of this analytical study indicate that the generators on the Chicago system may be operated safely at high power factors.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.