Abstract

THE PURPOSE of the article is to discuss an updated survey of the technical condition of porcelain high-voltage insulators of the type IOS 110/400, which had defects with partial discharge intensities above 4 nC, at Tatenergo substations. The experiments were carried out with simultaneous use of electromagnetic and acoustic research methods.During the analysis of the RESULTS obtained, the influence of the fields of previous powerful partial discharges on the technical condition of high-voltage insulators was established. The physical features of detecting powerful partial discharges by electromagnetic and acoustic methods have been studied. The conducted studies allow us to draw the following.CONCLUSIONS: the previous partial discharges can create additional long-lived electric fields on the dielectric surfaces of defects that exceed the field of the applied operating voltage in intensity; the necessity of using both physical methods simultaneously in the examination of high-voltage insulators in operation is shown.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call