Abstract
The paper presents the application of a UPFC to a case study of a 12-bus high power network. The UPFC shunt converter employs 8 3-level Neutral Point Clamped (NPC) voltage source converters (VSC) and 12 single-phase three-winding phase shifting transformers (PST), generating a 48-pulse output voltage. The 3-phase H-bridge series converter shares the same dc-link with the shunt one. The novel feature of this work lies in the use of a model-based generalised predictive current control law to the shunt converter for voltage and power flow control which has shown superior performance without additional filters compared to a P+I control scheme. In addition with the phase shift and switching angle control of each NPC-VSC output voltage, the topology offers improved harmonic performance and a zero-sequence blocking transformer is used for total triplen harmonics elimination.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.