Abstract

In order to ensure the safe and stable operation of gas insulated switchgear (GIS), a new method for identifying the type of partial discharge in GIS is proposed. First, the GIS partial discharge experimental platform produced four partial discharge signals. Second, the energy moments are calculated at each frequency to produce the frequency division features after the four partial discharge signals have been decomposed using variational modal decomposition (VMD). Finally, the type of GIS partial discharge is determined using the LSTM model enhanced by the quantum cuckoo search (QCS) algorithm. The experimental results show that the proposed method can successfully identify four types of partial discharge in GIS with an accuracy of 99%.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.