Abstract
A detailed full-scale survey of building structures was carried out as a part of scientific and technical support on changing the functional purpose of building premises built in the 1950s. The purpose of the technical condition survey was to assess the bearing capacity of structures and develop conditions for mechanical building safety. Special attention was paid to the study of floor-to-floor overlapping. Over a long period of operation, numerous changes were made to the original structural solution of the building. These changes transformed the design scheme of static work of structures, floors in particular. Due to the multifactorial and difficult-to-control conditions, it wasnt easy to determine the actual bearing capacity of the overlaps with the required degree of reliability using the existing calculation methods. Therefore, in order to confirm the proposed design assumptions, full-scale tests of the overlaps were carried out by loading, which confirmed their bearing capacity determined by the calculation. The conducted field tests made it possible to avoid expensive reinforcement of structures and extend the building life.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.