Abstract

The paper describes full-scale fire-fighting tests performed in an underground mine. A total of six different methods to fight a full scale fire in a mine tunnel were tested. The methods involved different fire-fighting equipment but were comparable regarding fundamental conditions such as length of response-route, fire-fighting set-up, and smoke and fire size. The aim was to compare different equipment and methods to reach and eventually extinguish the fire. Fire fighters using breathing apparatus (BA) were monitored regarding air consumption, movement speed and local actions and decisions. The results are presented and analyzed in respect to fire-fighting efficiency, front BA operations including moving speed and performed actions, as well as the time to successfully put out the fire. Measurements of heat release rates, temperatures and moving speeds are given in order to quantify the efficiency of the operation. Results indicate that a timespan of 15–30 min is needed for the firefighters to reach the fire source and achieve the extinguishing criteria in five of the tests. The standard equipment and nozzles shows good performance in the tests. A limiting factor on the firefighter’s endurance is the amount of air that is available. As a result from these findings the endurance of BA-teams could improve if focus is put on team organization, lightweight equipment and air supply.

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.