Abstract

It is hard to accurately meter the fuel feed into the furnace for a double-in and double-out pulverizing system, which affects the fuel control quality and also the main steam pressure of a boiler. A correction method for the indirect measurement model of the coal metering feed into the furnace for double-in and double-out pulverizing system is proposed based on the combustion state diagnosis of a burner using fuzzy C-mean clustering method, of which is applied in a 620MW super critical power unit. The engineering application results suggested that the method of this work is effective to improve the fuel control quality during the mill start and stop process. By using the method of this work, the controlling deviation between the target value and the measured value of the main steam pressure is within 0.2 MPa, while it is about 0.6 MPa when the fuel control is without correction.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.