Abstract
AbstractThe frequency distribution of the crest values of overvoltage waves in low voltage AC power circuits can be approximated by an exponential function. The flashover probability P of a clearance with an impulse withstand voltage Ǔst in an electrical equipment is given by P= exp (‐ α Ǔst). The annual number of flashovers of a single clearance in an unprotected house wiring system supplied by an unprotected overhead network depends upon the impulse withstand voltage, the latitude of the network, the annual number of thunderstorm days, the effective length and the height above ground of the overhead line. However, this does not mean, that every flashover triggers a dangerous power frequency follow current.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.