Abstract
Quantities related to the response of grounding electrodes subject to lightning currents are simulated under the assumption of constant and frequency-dependent soil resistivity and permittivity for 100-4000 Ω·m soils, using an accurate electromagnetic model. It was found that the frequency dependence of soil parameters is responsible for decreasing the grounding potential rise of electrodes and, thus, their impulse impedance and their impulse coefficient. This effect is more pronounced with increasing soil resistivity and for typical currents of subsequent strokes. The reduction of these quantities is negligible for soils of 300 Ω·m and below. It is considerable for soils above 500 Ω·m and is very significant above 1000 Ω·m. Reductions of around 23%, 30%, 40%, and 52% are found, respectively, for soils of 600, 1000, 2000, and 4000 Ω·m and typical subsequent stroke currents. Lower values, around 8%, 11%, 18%, and 28%, are found for first stroke currents.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
More From: IEEE Transactions on Electromagnetic Compatibility
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.