Abstract

The impedance of the virtual synchronous generator (VSG) is an effective method to analyze the dynamic interactions between the VSG and the grid. For the existence of power controllers and asymmetric inner-loop controllers in the d- and q-axis, there are couplings in the output sequence impedance of VSG. Although the couplings are relatively small, they still have a significant impact on the stability performance. However, there is no result published on this aspect up to now. To bridge this gap, a sequence impedance model based on harmonic linearization is established in this paper, which explicitly reveals the mirror frequency effect (MFE) in VSG. Subsequently, the relationships between the power controllers and the MFE are demonstrated. Finally, simulation results verify the feasibility and correctness of the theoretical analysis presented above.

Full Text
Published version (Free)

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call