Abstract

The conducted as well as the induced voltages on control cables and control circuits due to transient electromagnetic (EM) fields generated during switching operations in a gas-insulated substation (GIS) depend on the waveshape of the very fast transient overvoltages and the associated very-fast transient currents (VFTCs). The aim of this paper is to build a basis for characterizing the VFTC generated in gas-insulated switchgear and the associated equipment during switching operations for the study of transient coupling phenomena. The peak magnitudes of VFTC and their dominant frequency content at various locations have been computed in a 245-kV GIS for different switching operations as well as substation configurations. Finally, the influence of the substation layout on the frequency spectrum, dominant frequencies, and the highest possible frequency component of the VFTC at various distances from the switch have been reported.

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.