Abstract

An experimental investigation of the steady-state rates of heat loss from an array of vertical rectangular fins of 3 mm thickness and 250 mm length, when in the presence of an almost adiabatic horizontal shroud, situated adjacent to and above the horizontal fin tips, is reported. With the fin's horizontal base at a uniform temperature of 40 ± 0·1° C above that of the ambient environment, the optimal fin separation—corresponding to the maximum rate of heat loss—is deduced. As the ratio of the shroud height above the vertical fins to the fin height decreases from unity to zero, this optimal value decreases by approximately 17%. The frictional characteristics of the air flow through the fin array have also been studied in the Reynolds number range of 4·0 × 10 4 to 2·0 × 10 5. Large streamwise pressure drops and high heat-transfer rates resulted when the fins were closely spaced and no clearance gap was present above the vertical fins. In reasing the shroud clearance resulted in smaller overall pressure drops and decreasing heat-transfer rates from the heat exchanger.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.