Abstract

Partial discharge (PD) in liquid nitrogen (LN2) insulation is a key issue in cryogenic or high-temperature superconducting power apparatus. In this letter, we experimentally demonstrate PD identification in LN2 using a fluorescent optical fiber sensor and compare its sensitivity to the conventional ultrahigh frequency (UHF) technique. The Corona inception voltage (CIV) in LN2 is studied under fundamental ac and harmonic ac voltages with different values of total harmonic distortion (THD). It is observed that CIV reduces with the increase in harmonic voltage with higher THD. Phase resolved partial discharge pattern, peak-to-peak voltage, and the energy content due to corona discharges measured by both fluorescence-based and UHF techniques follows the same trend, indicating the viability of the new technique.

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.