Abstract

An experiment on a refrigerant two-phase flow in a horizontal pipe was performed for flow pattern observation and void fraction measurement. Refrigerants used were R12 and R22, and the saturation pressure range was from 5.7 to 19.6 bar. From obtained data it was found that the flow pattern of the refrigerant two-phase flow can be presented on a revised Baker map, where the property correction factor on surface tension was modified. It was also found that the influence of the shut-off speed in void fraction measurement is negligible. Experimental data on void fraction agree well with Zivi, Thom and Baroczy correlation approximated by Butterworth.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.