Abstract
Based on the study of gross flow maldistribution in an experimental electrical heater, this paper presents the effect of flow nonuniformity on the performance of heat exchangers. First, it is shown that it is much more important to understand maldistributions for electrical heaters than for two-fluid heat exchangers. The study of the flow distribution in a particular heater shows that reverse flows may occur for poor inlet header design. Suggested here is a simple way to homogenize the flow distribution and a simple law to calculate, with good accuracy, the velocity ratio (ratio of the highest velocity in the tubes to the lowest velocity). The original fluid distribution is applied to heat exchangers (condensers, counterflow and crossflow heat exchangers), and it is shown that gross flow maldistribution leads to a loss of effectiveness of about 7% for condensers and counterflow heat exchangers, and up to 25% for crossflow exchangers, for velocity ratios up to 15.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.