Abstract
The isothermal flow losses through an array of A-frame finned tube heat exchangers are determined experimentally. Correlations that describe these losses are derived from scale-model tests conducted on different V-bundle configurations, each simulating a section of a typical A-frame array. The experimental data are then compared with test data obtained from a full-scale heat exchanger installation. It is found that the downstream flow losses behind a V-bundle section are significantly influenced by the semiapex angle, the process stream duct diameter, and the distance between the A-frames.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.