Abstract

In order to clarify the effect of tip clearance (TC) size on fan performance and the flow field at rotor outlet in a small semi-open axial fan, the experimental investigation was carried out. The tip diameter of test fan rotor was 180mm and test TC sizes were 1mm (TC=1mm) and 4mm (TC=4mm). Fan characteristics tests were carried out for two cases of TC size and three-dimensional velocity fields at rotor outlet were measured using a single slant hot-wire probe at four flow-rate conditions. As a result, it was found that the pressure — flow-rate characteristics curves for two cases showed almost the same tendency. However, the ensemble averaged velocity profiles along radial measurement stations of TC=4mm largely changed compared with that of TC=1mm in cases of small flow-rate condition. From the phase-locked averaging results, it was also found that the vortex existed in the rotor outlet flow field of high flow-rate condition for each TC case. Compared with the vortices for TC=1mm and TC=4mm, the vortex for TC=4mm was stronger than that for TC=1mm.