Abstract

Static electrification has been suspected to be at the origin of serious incidents in power transformers. In fact, the oil flow electrification phenomenon in power transformers induces charge accumulation in pressboard and then increases its surface potential. In some unknown conditions, this potential can induce some electrical discharges and then serious failures in power transformers. This paper presents the results, which are one part of a work made in the L.E.A. for the best understanding of this problem. The influence of the temperature gradient on the space charge distribution and accumulation in the pressboard is studied by two special set-ups performed in the laboratory. Also, it seems that temperature increases charge accumulation magnitude inside the pressboard, but the charge distribution deep in the pressboard seems to be non dependent of gradient temperature.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.