Abstract

Experiments on flow boiling heat transfer and critical heat flux (CHF) of the dielectric coolant FC-72 are carried out for four in-line simulated electronic chips of 10 mm × 10 mm, for both flush-mounted and protruded chips on one wall of a vertical rectangular channel. The fluid velocity and subcooling are varied from 4.2 to 78 cm/s ( Re L =1.0×10 3 to 3.0 × 10 4), and from 15 to 33°C, respectively. The fully-developed nucleate boiling regime is not affected by changes in flow velocity and subcooling, whereas the surface temperatures decrease with increasing flow velocity and subcooling in the partial boiling regime. CHF generally increases with the degree of subcooling and with velocity at higher inlet velocities, but velocity has little effect at values less than 20 cm/s. The surface temperatures for the flush-mounted chips are lower than those for protruding chips, and the CHF data for the flush-mounted chips are higher than those for protruding chips; the differences between these two cases increase with increasing velocity.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.