Abstract
Bench‐scale and pilot‐plant studies were used to investigate the effects of flocculation time and floe size on the performance of dissolved air flotation and to determine air requirements for three different types of water supplies. The results show that long flocculation periods are not needed and suggest that floe particles of 10–30 μm should be prepared for flotation. Two measures of the air supplied were examined: percentage recycle and the bubble volume concentration or the volume of air released per volume of water treated. Bubble volume concentrations of 4,600 ppm or 8 percent recycle were sufficient to effectively treat all the waters tested.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.