This paper proposes a strategy of flicker mitigation for doubly-fed induction generator (DFIG) wind turbine systems. In the weak grid system where the grid impedance ratio is low, the reactive power compensation only cannot suppress the flicker sufficiently due to the limited power capacity of the converters or the DFIG. For the full suppression of flickers, the active power smoothening using the energy storage system (ESS) needs to be utilized together with the reactive power compensation. The effectiveness of the proposed method is verified by PSCAD/EMTDC simulation results for a 2[MW] DFIG wind turbine system and by experimental results for a 3[kW] wind turbine simulator.

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.