Abstract

This paper presents a flicker mitigation scheme for the doubly-fed induction generator (DFIG) during variable wind conditions. The flicker mitigation strategy was developed based on the distribution line X/R ratio and the active power deviation from the average active power during variable wind conditions. Flicker emission was analyzed using a flicker meter based on the IEC standards. Both short-term and long-term flicker severities were analyzed during the time period of study. The flicker mitigation strategy was evaluated under different system conditions such as X/R ratio, distribution line length, short-circuit capacity (SCC), and wind variability. It is shown that the proposed control scheme mitigates flicker severity with different X/R ratios, distribution line lengths and different wind conditions. However, the proposed strategy is less effective with relatively low SCCs at the point of grid connection, due to large fluctuations of the voltage at the point of grid connection.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.