Abstract

AbstractA flexible smart coating with electroluminescence effect was designed and fabricated on the surface of gas insulated switch gear (GIS)/gas insulated transmission line (GIL) epoxy insulators based on two‐step curing process. As the AC voltage increases, the luminous area on the insulator surface expands from the centre to the periphery, and the light intensity shows a linear relationship with the applied voltage. Besides, the flexible smart coating can effectively identify the location of metal particle defects and the degree of electric field distortion. The flexible smart coating enhances the surface flashover voltage due to its higher dielectric constant. Simultaneously, metal particle contamination can substantially reduce the insulation performance of epoxy insulators, particularly when they are located near the high‐voltage side. It is hoped that this study can provide a reference for the smart detection of surface defects GIS/GIL basin insulators.

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.