Abstract

AbstractA waste gas incinerator experienced a flashback with a pressure wave in the Suction Vent Gas (SVG) system. Extensive damage resulted to the SVG flame arrestor, SVG fan, SVG valves, and incinerator piping. There were no injuries. The primary cause of the incident is believed to have been a fuel rich SVG stream that was rapidly introduced into the incinerator creating a “puff.” This “puff” allowed flame from the natural gas ring burner to blow back into the windbox igniting the fuel rich SVG. The combustion of gas in the ducting then created a pressure wave that blew apart the flame arrestor and caused the remainder of the damage.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.