Abstract

In Hong Kong, air-conditioning (A/C) systems are major consumers of electricity. Although water-cooled air-conditioning systems (WACSs) are more energy efficient, the need for water towers, water treatment and other operation and maintenance (O&M) demands restrain their application in most buildings. This paper reviews a pilot application of treated effluent from sewage treatment works as a cooling medium for the Direct Expansion type of A/C system within the treatment Plant. The Drainage Services Department (DSD) installed a WACS with a self-assembled effluent-cooled condenser to study the energy efficiency, cooling performance and actual O&M requirements of the new system over a one-year pilot. It revealed that an energy saving of up to 27.6% per year could be achieved when compared with a conventional air-cooled air-conditioning system (AACS). This innovative effluent cooling A/C system achieves innovative reuse of treated effluent as well as reduction in carbon footprint as a result of higher energy efficiency for sustainable development.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.