Abstract

Based on the ISO 834–1 standard code, this study examined the fire insulation and fire integrity properties of two full‐scale glass panes (a common tempered glass pane and a non‐heat‐resistant fireproof glass with the same dimensions 120 cm × 240 cm × 0.5 cm) covered with a water film in a standard full‐scale 3 m × 3 m door/wall refractory furnace. For fire testing in the standard furnace, a specialized testing frame was devised to accommodate the multi‐nozzle spray system with a buffer box, which generated a down‐flowing water film on the glass surface. When a water film with adequate thickness (∼1.5 mm) and flowing speed (∼0.7 m/s) was established on a glass pane, the evaporative latent heat of the water film could be used to protect the glass from melting or breaking in a fire. In this study, the period of fire insulation and integrity could be extended to 100 minutes and the temperature of the glass surface was kept below 210°C. Thus, the substitution of a common non‐fire‐resistant tempered glass with water film for fireproof glass or overhead doors has been proven workable.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.