Abstract

A method is presented for calculation of ampacity of cable in fire protection wrapped cable trays. A brief description of the model is presented. The iterative technique used for solution of the model's simultaneous transcendental equations is presented with a description of the computer program. Cable derating for several typical installations is given and a graph is developed for use with ICEA P-55-440. To use the graph, the only data needed are the wrap thickness-to-conductivity ratio and emissivity. Ampacity derating derived from the model is also compared with published test results for two different fire wrap systems. >

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.